Air Differential Pressure Switch
SK6021 pressure switch can be used to sense
(Differential) pressure and flow of air in ducts and pipes
.Typical applications include:
-Filter obstructive alarm.
-Air proving in ventilation ducts.
-Maximum air flow controller for variable air volume
systems.
-Burner air control
Specifications
Product name | Waterproof Switch Air Differential Pressure Switch |
Media | Air,non-combustible and non-aggressive gas |
Max Operating Pressure | 10 kPa |
Mounting Position | Diaphragm in any vertical plane |
Degree of protection | IP54 (with cover) |
Operating Temperature | -40° C to 85° C |
Contact Arrangement | SPDT |
Electrical Rating |
Resistance: Initial: < 50 milliohms; Current:1.5A resistive(0.4A inductive) @ 250V |
Electric Connection | 6.3 x 0.8 blade 46244 or screw terminals |
Material |
Housing: ABS Duct connectors: ABS Membrane: Silicone Cable sleeve: PVC |
Weight | 0.15kg(0.35kg with flexible pipe) |
Connection | 6.0mm Dia. for tube connection |
Approval | UL, CE, RoHS |
Measuring Range
SK6021-B: 30Pa-300Pa,
SK6021-C: 50Pa-500Pa,
SK6021-D: 100Pa-1000Pa
Mounting instruction
The switch is preferably mounted with the diaphragm in a vertical plane , unless the device is set or calibrated for horizontal mounting as on special customer models . On these models the mounting position is indicated on the side of the control .It may
be fastened directly to the duct , heater or panel as long as the mounting surface has minimal or no vibration .Pressure connection ns are marked +(high pressure ) and - (low or static pressure).For more informaton, please read the diagram on the side of the control .